Installation Procedure

Tubing Permissible Length & Height Difference

Please refer to the attached manual of outdoor units.

Tubing Materials & Specifications

Refrigerant Filling Amount
Add the refrigerant according to the installation instruction of outdoor unit. The addition of R22

refrigerant must be performed with a measure gage to ensure the specified amount while compressor

failure can be caused by filling too much or little refrigerant.

Connecting Procedures of Refrigerant Tubing
Proceed the flare tube connecting operation to connect all the refrigerant tubes.

Outer

Diameter of

Tubing (mm)

Mounting

Torque (N-m)

Increase mounting

Torque (N-m)

6.35

9.52

12.70

15.88

19.05

11.8(1.2kgf-m)

24.5(2.5kgf-m)

49.0(5.0kgf-m)

78.4(8.0kgf-m)

98.0(10.0kgf-m)

13.7(1.4kgf-m)

29.4(3.0kgf-m)

53.9(5.5kgf-m)

98.0(10.0kgf-m)

117.7(12.0kgf-m)

Dual wrenches must be used in the connection

of indoor unit tubing.

Mounting torque refers to the right table

Cutting and Enlarging

Cutting or enlarging pipes should be proceeded

by installation personnel according to the

operating criterion if the tube is too long or flare

opening is broken.

Vacuumizing

Vacuumize from the stop valve of outdoor units

with vacuum pump. Refrigerant sealed in indoor

machine is not allowed to use for vacuumization.

Open All Valves

Open all the valves of outdoor units. [NB: oil

balancing stop valve must be shut up completely

when connected one main unit.]

Checkup for Air Leakage

Check if there is any leakage at the connecting part

and bonnet with hydrophone or soapsuds.

Connecting

1. Connecting circular terminals:

Connecting

circular terminals:

The connecting method of circular terminal is

shown in the Fig. Take off the screw, connect it

to the terminal tier after heading it through the

ring at the end of the lead and then tighten it.

2

.

Connecting straight terminals:

The connection methods for the circular terminals

are shown as follows: loosen the screw before

putting the line terminal into the terminal tier,

tighten the screw and confirm it has been clamped

by pulling the line gently.

3

.

Pressing connecting line

After connecting line is completed, press the

connecting line with clips which should press on

the protective sleeve of the connecting line.

correct

pressing

terminal tier

pressing clip

wrong

pressing

Tubing

Material

Model

Tubing Size

(mm)

Gas pipe
Liquid pipe

AB184~

244FCAHA

AB424~

484FCAHA

12.70

6.35

9.52

15.88

9.52