3. PREPARATION FOR THE INSTALLATION

(1) Position of ceiling opening between unit and suspending bolt.

3

18

AB424FCAHA AB484FCAHA

(2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.)

(3) Install a suspending bolt.
(Use a M10 bolt)

To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new

ceiling, use built-in type bolt or parts prepared in the field.

Before going on installing adjust space between ceiling.

Note: All the above mentioned parts shall be prepared in field.

Ceiling

50~100

Roof

Anchor bolt

Long nut
Suspending bolt

Refer to paper pattern for dimension of ceiling hole.

Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before installation.

Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration.

Contact your real estate dealer

AB184FCAHA AB244FCAHA

950(Ornament panel)

890(Ceiling opening)

840(Indoor unit)

680

(Distance between suspending bolts)

(Distance between suspending bolts)

950(Ornament panel)

890(Ceiling opening)

840(Indoor unit)

Suspending bolts

Refrigerant pipe

*

*

680

A

Note:

Dimension of ceiling opening marked with * can be as

large as 910mm, but the matching part of ceiling with

ornament panel shall be over 20mm.

20 Over

(160)

Suspending bracket

Ceiling

A

780

(Distance between suspending bolts)

620

(Distance between suspending bolts)

860-890

860-890

(Ceiling opening)

AB094FAAHA AB124FAAHA

807.6

761

700

350

438

500(GRILLE)

460

712.6

831

860(GRILLE)

£¤

Ceiling opening)