beautypg.com

B) connection to a closed loop system, Fig. 5, Kml-700mwh-m connection to a closed loop system – Hoshizaki KML-700MWH-M User Manual

Page 12

background image

12

Condenser Return Line

Shut-Off Valve

Condenser Return Line

Drain Valve

Icemaker

Drain Outlet

3/4" FPT

Icemaker

Water Supply

Inlet

1/2" FPT

Fig. 5

Condenser

Water Supply

Inlet

1/2" FPT

Condenser

Return Outlet

3/8" FPT

Separate piping to approved drain.

Leave a 2-inch (5-cm) vertical air

gap between the end of each pipe

and the drain.

Icemaker

Bin Drain Outlet

3/4" FPT

2-inch (5-cm) air gap

Floor Drain

Bin

Icemaker Water Supply

Line Shut-Off Valve

Icemaker Water Supply Line

Drain Valve

Condenser Water Supply Line

Shut-Off Valve

Condenser Water Supply Line

Drain Valve

KML-700MWH-M

Connection to a Closed Loop System

b) Connection to a Closed Loop System
• Condenser water supply inlet is 1/2" female pipe thread (FPT). A minimum of 3/8" OD

copper tubing is recommended for the condenser water supply line.

• Condenser return outlet is 3/8" FPT. A minimum of 3/8" OD hard pipe is recommended for

the condenser return line.

• Shut-off valves and drain valves should be installed at both the condenser water supply

inlet and condenser return outlet.

• The water supply to the condenser should not drop below 4 GPM.
• The pressure differential between the condenser water supply inlet and condenser return

outlet must be no less than 10 PSIG.

• When using a glycol blend, the solution mixture should be less than 30% glycol.
• In order to maintain the proper high side pressure, the condenser water supply inlet

temperature should not drop below 45°F (7°C) and the condenser return outlet
temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker
installation is complete, confirm the condenser return outlet temperature 5 minutes
after a freeze cycle starts. If the outlet temperature is not in the proper range, adjust the
water-regulating valve to bring it into range.