Water-cooled condenser, A) connection to an open drain system – Hoshizaki KML-700MWH-M User Manual

Page 11

background image

11

Fig. 4

KML-700MWH-M

Connection to an Open Drain System

2. Water-Cooled Condenser

a) Connection to an Open Drain System
• Condenser water supply inlet is 1/2" female pipe thread (FPT). A minimum of 3/8" OD

copper tubing is recommended for the condenser water supply line.

• A condenser water supply line shut-off valve and drain valve should be installed.
• Condenser drain outlet is 3/8" FPT. A minimum of 3/8" OD hard pipe is recommended for

the condenser drain line.

• In some areas, a back flow preventer may be required in the cooling water circuit.

Separate piping to approved drain.

Leave a 2-inch (5-cm) vertical air

gap between the end of each pipe

and the drain.

Icemaker Water Supply Line

Shut-Off Valve

Icemaker Water Supply Line

Drain Valve

Icemaker

Icemaker

Water Supply

Inlet

1/2" FPT

Bin Drain Outlet

3/4" FPT

2-inch (5-cm) air gap

Floor Drain

Icemaker

Drain Outlet

3/4" FPT

Bin

Condenser Water Supply Line

Shut-Off Valve

Condenser Water Supply Line

Drain Valve

Condenser Water

Supply Inlet

1/2" FPT

Condenser

Drain Outlet

3/8" FPT