beautypg.com

Honeywell EXCEL 10 W7751H User Manual

Page 6

background image

EXCEL 10 W7751H SMART VAV ACTUATOR

95-7553—04

6

Fig. 10. Power wiring for multiple controllers.

Fig. 11. 201052 Auxiliary Switch mounted on W7751H.

NOTES:

If a range stop pin is used, it must be pointing

inward toward the shaft (see Fig. 11) to allow

clearance for the auxiliary switch.

Each switch is independently adjustable in two-

degree increments to any point within the travel of

the actuator. Switches have a fixed differential of

approximately three angular degrees.

PROCEDURE

1. Determine desired switching action (i.e, if switch

energizing is to occur during CW or CCW rotation). With

switch cam as shown in Fig. 12, the normally closed

contact opens in CCW rotation. The normally open

contact closes. Conversely, with switch cam as shown

in Fig. 13, the normally closed contact opens during CW

rotation and the normally open contact closes.

Fig. 12. Switching configuration for CCW rotation

(top view).

Fig. 13. Switching configuration for CW rotation

(top view).

2. Align switch hub with actuator set screws. Mount switch

on actuator and tighten the three captive screws.

3. Connect controller with laptop PC. To do this, the

controller on the W7751H must be wired, powered, and

connected to the portable PC via the SLTA. The SLTA

connects to the controller on the W7751H via Network

Access Jack on the T7770 Wall Module or by B-Port on

the Q7750A Zone Manager. From E-Vision Software,

drive the W7751H actuator and halt the motion at the

desired position for switch operation.

NOTE: When installed, angular position indicator on

the switch face moves from 90 to 0 degrees

during CCW motion and from 0 to 90 degrees

during CW motion.

4. Once finished programming, disconnect the portable

PC.

5. With a screwdriver, move the cam inside the switch

assembly to the appropriate position, remembering cam

travel direction for switching purposes (see Fig. 14)

when turning switch on or off. Monitor switch closure

with ohmmeter for a continuity check. Normally closed

contact should measure zero ohms and normally open

contact should measure infinite ohms when switch is not

activated. The opposite is true when switch is activated.

M10524A

28

W7751B

W7751H OR J

24

VAC

120/240

VAC

TRANSFORMER

EARTH

GROUND

EARTH

GROUND

1 2 3 4

1 2 3

9 10

W7751D,F

32

EARTH

GROUND

EARTH

GROUND

1 IF THE W7751 CONTROLLER IS USED IN UL 1995 EQUIPMENT AND THE

PRIMARY POWER IS MORE THAN 150 VOLTS, GROUND ONE SIDE

OF TRANSFORMER SECONDARY.

1

24V

COM

24V

COM

24V

COM

N

C

N

O

COM

RANGE STOP PIN

POINTED TOWARD

SHAFT

201052 AUXILARY

SWITCH

0

15

30

45

60

75

90

M10005

COM

NO
NC

M2160

CCW

COM

NO

NC

M2161

CW