Shrouds, A. radiation shield, B. field constructed shrouds – Heat & Glo Fireplace HEAT & GLO PIER-40 User Manual
Page 36
36
3 in. (76 mm) tall legs
Ø 17 1/2 in. (444.5 mm) Round Hole to fit over cap
Length x Width to fit inside shroud
Figure 10.1 Radiation Shield
10
Shrouds
• Chase top shrouds may be field constructed where
permitted by regional building codes.
WARNING! Risk of Fire! Shrouds must be constructed
as specified. Improper construction may overheat chase
top.
NOTICE:
Some regional codes require an agency-Listed
shroud. Consult your local building officials.
• Hearth & Home Technologies supplies UL listed shrouds.
See your dealer for details.
• The following field constructed shroud designs have
been tested for Hearth Technologies fireplace systems
and termination caps.
• The shrouds must be constructed from a minimum .018
in. (26 ga) thick aluminized steel.
A. Radiation Shield
• Some shrouds require a radiation shield. Use where
specified.
• Radiation shield must be constructed of minimum 26 ga
sheet metal.
3 in (76 mm)
minimum
Min.
Base Dim.
Min.
Base Dim.
Min.
Top Dim.
Min.
Top Dim.
Min. Opening
Width
Min. Opening
Width
Figure 10.2 Open Top Shroud Dimensions
B. Field Constructed Shrouds
• The wire mesh is optional but recommended and must
be .018 in. thick minimum, 1/2 in. mesh.
Heat & Glo • BAY-40, PIER-40 • 34977 • Rev AE • 05/07/13
TR11/11T
TR11/11T TV
Min. Base Dims.
in
32 x 32
26 x 26
mm
813 x 813
660 x 660
Radiation Shield
Required
Min. Top Dims.
in
29 x 29
23 x 23
mm
737 x 737
584 x 584
Min. Opening Width
in
26 x 26
20 x 20
mm
660 x 660
508 x 508
Open Top Shroud (TR11/TR11T caps require radiation shield)