T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS

Table 2. Thermostat Installer Setup Options.

a

Available on select models.

b

Installer Setup Number 02 must be set to 01 to extend fan operation.

(Continued)

Installer Setup

Number

(Press

i

key

Factory-Setting

Other Choices

(Press

or

key to change)

Actual

Select

to change)

Display

Description

Display

Description

Setting

Not used

01

Fan operation

a

02

00

Conventional applica-
tions where equipment
controls fan operation in
heat mode

01

Heat pump and electric heat
applications where
thermostat controls fan
operation in heat mode

Not used

03 and 04

Stage-two
heating cycle
rate

05

06

6 cph used for
conventional systems

01, 03,
or 09

01—1 cph used for radiant

floor heat, gravity systems

03—3 cph used for hot water

systems or high efficiency
furnaces

09—9 cph used for electric

heat systems

Not used

06 thru 11

Changeover
(T8524D only)

12

01

Manual changeover

00

Automatic changeover

Not used

13

Degree
temperature
display

14

00

Temperature is
displayed in °F

01

Temperature is displayed in
°C

Not used

15 thru 18

Extended fan
operation in
heating

a,b

19

00

No extended fan
operation after the call
for heat ends

01

Fan operation is extended
90 seconds after the call for
heat ends

Extended fan
operation in
cooling

a

20

00

No extended fan
operation after the call
for cool ends

01

Fan operation is extended
90 seconds after the call for
cool ends

Not used

21 thru 23

Outdoor
temperature
display

a

24

00

No outdoor temperature
is displayed

01

Outdoor temperature is
displayed. Needs a
C7089B1000 Outdoor
Sensor to operate.

Not used

25 thru 29

Deadband

30

03

Heating and cooling
setpoints can be set no
closer than 3°F (1.5°C)

04 thru
10

Heating and cooling
setpoints can be set no
closer than the chosen
value:

04—4°F (2°C)
05—5°F (2.5°C)
06—6°F (3°C)
07—7°F (3.5°C)
08—8°F (4°C)
09—9°F (4.5°C)
10—10°F (5°C)

Not used

31 and 32

Minimum off
time for the
compressor

33

05

5 minute minimum off
time for the compressor

00, 01,
02, 03
or 04

Minimum number of minutes
(0 thru 5) the compressor will
be off between calls for the
compressor