beautypg.com

Caution, Installer setup, Temperature settings – Honeywell DMULTISTAGE T8524C User Manual

Page 4: T8524c,d multistage microelectronic thermostats

background image

69-1055—1

4

T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS

A combination of key presses are required to use the
Installer Setup feature.

To enter the Installer Setup mode, press and hold the
Information

i

key with the increase

and decrease

keys until the first number is displayed. All display

segments appear for approximately three seconds
before the number is displayed. See Fig. 9 and 10.

To advance to the next Installer Setup number, press
the Information

i

key.

To change a setting, use the increase

or de-

crease

key.

To exit the Installer Setup, press and hold the
Information

i

key until the display returns to normal

(approximately three seconds). The display scrolls the
numbers backwards to get to the normal display. The
Installer Setup is automatically exited if no key
presses are made for five minutes.

IMPORTANT

Only configurable numbers are shown on the
device. Example: If the thermostat does not have
a system key, Installer Setup Number 12 will not
be displayed. Review Table 2 factory-settings
and mark any desired changes in the Actual
Setting column. When Installer Setup in com-
plete, review the settings to confirm that they
match the system.

Fig. 8. T8524D system and fan keys location.

NOTE:

Always press the system and fan keys with your
fingertip or similar blunt tool. Sharp instruments
like a pen or pencil point can damage the
keyboard.

Temperature Settings

The default setpoint for heat is 70

°

F (21

°

C) and for cool is

78

°

F (25.5

°

C). Press the increase

or decrease

key to

change the present setting. To change between heat and
cool, press the Information

i

key until the setting to be

changed appears.

INSTALLER SETUP

NOTE:

For most applications, the thermostat factory-
settings do not need to be changed. Review the
factory-settings in Table 2 and if no changes are
necessary, go to the Installer System Test
section.

The Installer Setup is used to customize the thermostat to
specific systems. Installer Setup Numbers are listed in
Table 2. The table includes all the configuration options
available.

Fig. 7. T8524C system and fan switches location.

M10147

i

Press to select
heating or cooling
equipment.

Em. Ht.-Emergency heating
Heat— Heating equipment
Off — No equipment
Cool—Cooling equipment
Auto—Thermostat

automatically selects
heating and cooling
equipment.

Press to select
heating or cooling
equipment.

On

Fan runs continuously

Auto—Fan runs when

heating or cooling
equipment operates

System

System

System

Fan

Fan

Fan

1

1

CHECK LIGHT ON SELECT MODELS

M10105

MODE NUMBER DISPLAY
(COLUMN 2 OF TABLE 2)

FACTORY SETTING OR
OTHER CHOICE DISPLAY
(COLUMN 3 OR 5 OF TABLE 2)

Em HeatOffCool Auto Only

Heat Cool

OnAuto

System

Fan

Room

Outdoor

Em Ht Temporary Setting

Wait

%Humid

Aux Ht

Remote

Repl

Batt

M4844

M10146

i

HEAT OFF COOL

ON AUTO

HEAT OFF COOL

ON AUTO

SYSTEM

Selection for heating or cooling
equipment operation.

Heat - Heating equipment
Off - No equipment
Cool - Cooling equipment

FAN

On - Fan runs continuously
Auto - Fan runs when

heating or cooling
equipment operates

Fig. 9. Display of all the segments of the LCD.

Fig. 10. Display of Installer Setup mode and setting.

CAUTION

Electric heat systems must be configured to 01 in
Installer Setup 02 to prevent equipment damage
caused by the system running without the fan.