Gas information, Warning – Hearth and Home Technologies Dakota 42-CE User Manual

Page 9

background image

Heat & Glo Lifestyle Collection • Dakota 42-CE • 4036-915 Rev I • 11/07

9

6

6

Gas Information

Note: Gas line MUST be run from right side of fi replace.

WARNING

CHECK FOR GAS LEAKS
Fire Risk
Explosion Risk
Asphyxiation Risk
• Check

all

fi ttings and connections.

• Do not use open fl ame.
• After the gas line installation is complete,

all connections must be tightened and
checked for leaks with a commercially
available, non-corrosive leak check
solution. Be sure to rinse off all leak check
solution following testing.

Fittings and connections may have loosened
during shipping and handling.

WARNING

Fire Risk
Explosion Risk
High pressure will damage valve.
• Disconnect gas supply piping BEFORE

pressure testing gas line at test pressures
above 60 mbar.

• Close the manual shutoff valve BEFORE

pressure testing gas line at test pressures
equal to or less than 60 mbar.

A. Gas Pressure Requirements

Pressure requirements for Heat & Glo gas fi replaces are
shown in Table 1 below.

Two taps are provided on the outlet side of the gas control
for a test gauge connection to measure the inlet and outlet
pressures. These inlet and outlet pressure taps can be ac-
cessed through the internal valve access panels as shown
in Section 11: Maintaining and Servicing the Fireplace.

The fi replace and its individual shut-off valve must be dis-
connected from the gas supply piping system during any
pressure testing of the system at test pressures in excess
of 60 mbar.

If the fi replace must be isolated from the gas supply piping
system by closing an individual shut-off valve, it must be of
the handle-less type.

B. Gas Connection

Note: Have the gas supply line installed in accordance
with local building codes by a qualified installer
approved and/or licensed as required by the locality.

Table 1

Natural Gas

(G20)

Propane

(G31)

Butane

(G30)

Natural Gas

(G25)

Inlet Pressure

20mbar

37 or 50mbar

30 or 50mbar

25mbar

Manifold Pressure

4-8.7 mbar

24mbar

24mbar

8.7mbar

Gas Rate

1.68

m3

/

h

.62

m3

/

h

.42

m3

/

h

1.68

m3

/

h

Max.Input (NETCV)

16.5 kW

15.0 kW

13.7kW

14.0 kW

Burner Injector

DMS 25

DMS 44

DMS 46

DMS 25

Pilot Injector

51

30

30

51

Incoming gas line should be piped into the valve compart-
ment and connected to the ISO 7-Rp 1/2 (BSP Rp 1/2)
threaded gas inlet connection on the manual shutoff valve.

Note: Before the fi rst fi ring of the fi replace, the gas
supply line should be purged of any trapped air.

Note: Consult local building regulations to properly
size the gas supply line leading to the (Rp 1/2 in.)
hook-up at the unit.