Fireplace locations, A. fireplace minimum clearances – Hearth and Home Technologies Dakota 42-CE User Manual

Page 7

background image

Heat & Glo Lifestyle Collection • Dakota 42-CE • 4036-915 Rev I • 11/07

7

FP

= FIREPLACE OPENING

X

= AIR SUPPLY INLET

= AREA WHERE FIREPLACE IS NOT PERMITTED

O

N

P

R

Q

FP

(See Note 2)

___________________________________________________________________________

___________________________________________________________________________

___________________________________________________________________________

Q

MIN

R

MAX

Dakota

3.0 M

2 x Q

ACTUAL

1 additional termination cap

Q + 0.91 M 1 x Q

ACTUAL

2 additional termination caps Q + 1.83 M 2/3 x Q

ACTUAL

3 additional termination caps Q + 2.74 M 1/2 x Q

ACTUAL

R

MAX

= (2 / # caps plus fireplace ) x Q

ACTUAL

D

E

L

FP

A

H

M

X

J or K

I

A

G

F

FP

FP

FP

FP

FP

B

B

B

A =

0 cm . . . . . . . . . clearances above grade,

(See note 1) veranda, porch, deck or

balcony.

B

= 30.5 cm . . . . . . . clearances to window or door

that may be opened, or to
permanently closed window.

91.4 cm . . . . . . . vinyl windows or siding.

D** = 119.3 cm . . . . . . . vertical clearance to unventi-

lated soffit or to ventilated soffit
located above the terminal.

152.4 cm . . . . . . . vinyl clad soffits.

F

= 22.8 cm . . . . . . . clearance to outside corner.

G* = 15.2 cm . . . . . . . clearance to inside corner.

121.9 cm . . . . . . . vinyl windows or siding.

H

= 91.5 cm . . . . . . . not to be installed above a gas

meter/regulator assembly within
91.5 cm horizontally from the
center line of the regulator.

I

= 91.4 cm . . . . . . . clearance to service regulator

vent outlet and electric service.

J

=

22.8 cm . . . . . clearance to non-mechanical air

supply inlet to building or the
combustion air inlet to any other
appliance.

K

=

91.4 cm . . . . . clearance to a mechanical air

supply inlet.

L*** =

2.1 M . . . . . . clearance above paved sidewalk

(See note 1)

or a paved driveway located on
public property.

M**** =

119.3 cm . . . . . clearance under veranda, porch,

deck, balcony or overhang.

Not allowed: . . . . . . vinyl

N

=

15.2 cm . . . . . non-vinyl siding.

P = 213.3

cm

* 122 cm minimum for vinyl windows or vinyl siding.

** Not allowed for vinyl clad soffits.

*** a fireplace shall not open directly above a sidewalk or paved

driveway which is located between two single family dwellings
and services both dwellings.

**** only permitted if veranda, porch, deck or balcony is fully open

on a minimum of 2 sides beneath the floor, or if the screened
porch guidelines are followed.

Note 1: Local codes or regulations may require different clearances.

Note 2: Termination in an alcove space (spaces open only on one side

and with an overhang) are permitted with the dimensions
specified for vinyl or non-vinyl siding and soffits. 1) There must
be a 0.91 M minimum between terminations or between the

fireplace and termination. 2) All mechanical air intakes within 3.0
M of a termination must be a minimum of 0.91 M below the
fireplace hood. 3) All gravity air intakes within 0.91 M of the
fireplace hood must be a minimum of 2.54 cm below the termina-
tion.

A. Fireplace Minimum Clearances

Figure 4.1 Minimum Clearances

4

4

Fireplace Locations