9

3

Installing the Fireplace

Step 1. Locating the Fireplace

The diagram below shows space and clearance require-

ments for locating a fireplace within a room.

Minimum Clearances from the Fireplace to

Combustible Materials

Inches

mm

Glass Front .......................... 3 6.................914

Floor ....................................... 0 .................... 0

Metal Ends ........................... 1/2 .................1 3

Top .......................................... 3 ...................7 6

Ceiling* ................................. 3 1.................787

Figure 2. Fireplace Dimensions, Locations,

and Space Requirements

Figure 3. Framing Dimensions

Step 2. Framing the Fireplace

Fireplace framing can be built before or after the fireplace is

set in place. Framing should be positioned to accommo-

date wall coverings and fireplace facing material. The dia-

gram below shows framing reference dimensions.
CAUTION: MEASURE FIREPLACE DIMENSIONS AND

VERIFY FRAMING METHODS AND WALL COVERING

DETAILS BEFORE FRAMING.

NOTE: If an optional blower (Model FK-200) is to be

installed, a 12 x 12 inch (305mm x 305mm) access hole

must be framed into the wall (see Figure 3).

Minimum Clearances from the B-Type Vent Pipe

to Combustible Materials

Inches

mm

Vertical Sections. ............. 1 ................... 2 5

Horizontal Sections

Top ......................................... 1 ................... 2 5

Bottom .................................. 1 ................... 2 5

Sides ..................................... 1 ................... 2 5

At Wall Firestops

Top ......................................... 1 ................... 2 5

Bottom .................................. 1 ................... 2 5

Sides ..................................... 1 ................... 2 5

* The clearance to the ceiling is measured from the top

of the unit, excluding the stand-offs (see Figure 13).

36"

1"

36"

GLASS

GLASS

Clearance Requirements

The top and ends of the fireplace are defined by stand-offs.

The minimum clearance to a perpendicular wall extending

past the face of the fireplace is one inch (25mm). The metal

ends of the fireplace may NOT be recessed into combustible

construction.

Framing should be constructed of

2 X 4 lumber or heavier.

Model

A

B

C

ST-38GTV

39 5/8 38 3/4

21 1/16

NOTE: DIMENSIONS SHOWN IN INCHES

A

B

C

12"

12"

TOP VIEW