B. system components – Heat & Glo Fireplace ST-38GTV User Manual

Page 11

background image

11

!

!

Step 4. Installing the Vent System
A. Vent System Approvals

Model ST-38GTV is approved to use 5-inch (127mm)

diameter B-type vent. B-type vent must be used when the

vent system is within combustible construction.
This model may also use single wall rigid or flexible gas

vent IF and ONLY IF the vent system is installed within

non-combustible construction such as a masonry chimney.

The same diameter noted above for B-type vent must be

used for single-wall vent. See Figure 5.

B. System Components.

Vent System Configuration
MAXIMUM TOTAL HORIZONTAL RUN = 13 FT.
MAXIMUM TOTAL VERTICAL RISE = 10 FT.
MAXIMUM NO. of ELBOWS: 2 -90

o

plus 4 - 45

o

, or 8 - 45

o

.

Plan and install the vent system using the parameters shown

above.

WARNING: YOU MUST NOT EXCEED THESE

PARAMETERS.

Connect a B-Type vent component to the flue outlet collar.

Look at top inside of the firebox to check that the vent pipe

is attached to the unit. NOTE: It is always better to first

attach a straight section of vent to the unit before

attaching an elbow. Avoid using elbows in the vent

system if possible.
A 90-degree elbow can be attached directly to the unit. If it

is, it can be followed by a MAXIMUM 13-feet horizontal

run, a second 90-degree elbow ending in a vertical position,

and a MINIMUM 10-feet vertical rise ending in a listed

termination cap for the vent pipe.
Continue to add vent components, until the vent run is

completed.

WARNING: YOU MUST NOT EXCEED A TOTAL

MAXIMUM HORIZONTAL RUN OF 13 FEET FOR

THE ENTIRE VENT SYSTEM AND THERE MUST

BE A TOTAL VERTICAL MINIMUM RISE OF 10-

FEET IN ALL VENT SYSTEM CONFIGURATIONS

USED ON THESE FIREPLACES.

NOTE: The vent termination must be in a vertical

position and the termination cap must be listed for

the vent pipe used.

Figure 5. Vent System Attachment

!

Consult Local Building Code Officials and Codes for proper

vent system installations.

WARNING: THIS GAS FIREPLACE MUST NEV-

ER BE VENTED BY CONNECTING TO A CHIM-

NEY FLUE SERVING A SEPARATE SOLID FUEL

BURNING APPLIANCE.

B-TYPE

VENT PIPE

VENT COLLAR

LISTED

TERMINATION

CAP

LISTED

SINGLE-WALL

GAS VENT

NON-COMBUSTIBLE

CONSTRUCTION

13 FT.

MAXIMUM

10 FT.

MINIMUM