Voltage at Timer Terminals

Ac Voltage at

C-R Terminals

Possible Cause Check

Action

0 Vac

1. System power is Off.

1. Restore power.

2. Short in timer power supply wiring.

2. Replace wiring.

3. Limit switch contacts stuck open.

3. Free or replace limit switch.

4. Transformer supplying power is

burned out.

4. Replace transformer.

Up to 15 Vac.

1. System transformer used to power

the timer is inadequate.

1. Use additional (separate)

transformer.

2. Additional (separate) transformer

used to power the timer has
inadequate voltage.

2. Install transformer with proper

secondary voltage.

15 to 30 Vac.

1. Spring fingers on thermostat not

making proper contact with
subbase terminals.

1. Rebend spring fingers to a

45 degree angle to ensure
proper contact.

2. Timer has failed.

2. Replace thermostat.