To test the Beacon board place the test jumper to the “TEST” position. The board will then cycle through each output for 10
seconds. It will energize and de-energize the fan motor, electric heater, expansion valve and compressor for 10 seconds. When
in the TEST mode the status light flashes quickly. If a sensor is bad it will flash per the error chart. AT THE END OF THE TEST
RETURN THE JUMPER TO THE NORMAL POSITION.

PARTS LIST (Parts Dept. 800-686-7278)

HRPD PART

PART DESCRIPTION

NUMBER

Temperature Sensor

28900101

Transformer 208/240 - 24 volt - 40 VA

22522301

Transformer 208/240 - 24 volt - 75 VA (10HP + up)

22538401

Relay for condenser Fan or Crankcase Heater

22511401

Contactor for Compressor 40 amp with 24 volt Coil

2252440

Control Board for Electric Defrost

28910001

Control Board for Air Defrost

28910002

Terminal Block

2251266

Low Pressure Switch Time Delay Relay

22536801

Electric Expansion Valve

ESV 1 - 24 volt

29310001

ESV 2 - 24 volt

29310002

ESV 4 - 24 volt uni-polar valves

29310003

ESV 6 - 24 volt

29310004

ESV-8 - 24 volt

29310005

ESV-10 - 24 volt

29310006

ESV-25- 24 volt - bi-polar valve

29320001

Expansion Valve Molded Connector

29310007

Optional Pump-Down Switch

22510901

Beacon Smart Controller

89704401

Optional Smart Controller Software Package

89704501

Bi-polar adapter board (only used with 29320001

28920001

expansion valve)

BEACON OPERATIONAL LIMITS

Box set point tolerance ............................ +/-2

°

F

Down to -20

°

F outdoor ambient .............. Allows start-up & operation

Below -20

°

F outdoor ambient ................ Requires head pressure control valve

& pressure fan cycling switch
Controlling box temp. range .................... -25

°

F to 60

°

F

Voltage range at the board ...................... 18 VAC min / 30 VAC max
Surge protection at the board .................. up to 50 VAC