BEACON CONTROLLER
14
TABLE 3
The initial factory settings for the BEACON MICROPROCESSOR BOARD are indicated on the following
chart.
ELECTRIC DEFROST
AIR DEFROST
FACTORY SETTINGS
FACTORY SETTINGS
DEFROST CYCLES OR TIME
DEFROST CYCLES OR TIME
6 PER DAY/ 2 HRS
6 PER DAY/ 2 HRS
4 PER DAY/ 3 HRS
X
4 PER DAY/ 3 HRS
2 PER DAY/ 6 HRS
2 PER DAY/ 6 HRS
X
1 PER DAY/ 12 HRS
1 PER DAY/ 12 HRS
ELAPSED X
RUN TIME
ELAPSED X
RUN TIME
SUPERHEAT
SUPERHEAT
6
°
F
6
°
F
8
°
F
X
8
°
F
X
12
°
F
12
°
F
DEFROST FAIL-SAFE
DEFROST FAIL-SAFE
10 MIN
10 MIN
20 MIN
20 MIN
30 MIN
X
30 MIN
40 MIN
40 MIN
X
60 MIN
60 MIN
MEDIUM
X
LOW
MEDIUM
X
LOW
TEST
X
NORM
TEST
X
NORM
TYPE 1
TYPE 2
TYPE 1
TYPE 2
RESET TIME
X
NORM
RESET TIME
X
NORM
FORCED DEFROST
X
NORM
FORCED DEFROST
X
NORM
DEFROST END TEMP
DEFROST END TEMP
50
°
F
50
°
F
X
70
°
F
X
70
°
F
90
°
F
90
°
F
NOTE: When using the Beacon Smart Controller, the Defrost End Temperature for each Beacon board must
be set at 50
°
F. It is recommended that the room temperature pot for all the slave units be adjusted to the
maximum temperature 60
°
F when connected in a master/slave configuration.