® BUS WIRING GUIDELINES

3

74-2865—04

Table 1. Daisy-chain FTT Network Bus Topology Transmission Specifications (Doubly Terminated).

NOTES:

See Table 2 for singly terminated FTT network bus topology transmission specifications.

See Tables 3 and 4 for a list of Honeywell provided FTT daisy-chain and free topology network wire/cables.

See the generic cable manufacturer information that meets Echelon LonWorks Bus specifications in Table 5.

Table 2. FTT Network Free Topology Transmission Specifications (Singly Terminated).

Table 3. Honeywell Provided Daisy-Chain (Doubly Terminated) FTT Network Wire/Cables.

Table 4. Honeywell Provided Free Topology (Singly Terminated) FTT Network Wire/Cables.

NOTE:

Honeywell Cable, www.honeywellcable.com, is the recommended manufacturer of network wire.

Wire/Cable Type (Unshielded)

Cable Parameters

Maximum FTT Network Bus

Length for Segment(s)

C nF/km Vprop% of c AWG/Dia. RloopW/km

Honeywell Cable 1125 (stranded non-plenum) 79

67

16/1.5 mm

2

17.9

4600 feet (1400 m)

Belden 85102 (stranded non-plenum)

56

62

16/1.5 mm

2

28

8900 feet (2700 m)

Belden 8471 (stranded non-plenum)

72

55

Level IV Cable Specifications, 22AWG (solid/
stranded twisted pair)

49

67

22/.34 mm

2

106

4600 feet (1400 m)

TIA568A Category 5 24 AWG (twisted pair
solid or stranded, plenum or non-plenum)

46

58

24/.27 mm

2

168

3000 feet (900 m)

Wire/Cable type (Unshielded)

Maximum Length for Segment(s)

Node-to-Node

FTT Network Bus

Honeywell Cable 1125 (stranded non-plenum)

1640 feet (500 m)

1640 feet (500 m)

Belden 85102 (stranded non-plenum)

1640 feet (500 m)

1640 feet (500 m)

Belden 8471 (stranded non-plenum)

1300 feet (400 m)

Level IV Cable Specifications, 22AWG (solid/stranded twisted pair)

TIA568A Category 5 24 AWG twisted pair (solid or stranded, plenum or
non-plenum)

820 feet (250 m)

1500 feet (450 m)

Wire/Cable Type (Stranded Unshielded)

Maximum FTT Network Bus Length for Segment(s)

Honeywell Cable 3252 - plenum (one twisted pair)

4600 feet (1400 m)

Honeywell Cable 3253 - plenum (two twisted pair)

Honeywell Cable 1061 - non-plenum (one twisted pair)

Paige AK3797 - plenum (one twisted pair)

Paige AK3799 - plenum (two twisted pair)

Paige AK3798 - non-plenum (one twisted pair)

Wire/Cable Type (Stranded Unshielded)

Maximum Length for Segment(s)

FTT Network Bus

Node-to-Node

Honeywell Cable 3252 - plenum (one twisted pair)

1640 feet (500 m)

1300 feet (400 m)

Honeywell Cable 3253 - plenum (two twisted pair)

Honeywell Cable 1061 - non-plenum (one twisted pair)

Paige AK3797 - plenum (one twisted pair)

Paige AK3799 - plenum (two twisted pair)