Step 9: attaching the upper switch housing, Step 10: attaching the lower switch housing – Hunter Fan 41535-01 User Manual
Page 4
41535-01 10/8/2001
4
© 2001 Hunter Fan Company
FIGURE 13
FIGURE 14
Switch
Housing
Mounting
Plate
Housing
Assembly
Screw
Upper Plug
Connector
Upper Switch
Housing
B. Remove the screws from the motor hub. Insert one of
these screws in hole in blade bracket. Use a screw-
driver to hold in place. Align blade holes with mounting
holes in hub, by turning screw and readjusting blade
bracket until screw mates with threaded hole in hub.
Do not tighten until both screws have been put in blade
bracket. Repeat for all blades. See Figure 13.
C. A blade balancing kit has been provided with your fan.
Should the fan wobble in operation, you may use this
kit to correct the balance per the instructions supplied
with the kit.
Step 9: Attaching The Upper Switch
Housing
A. Partially install two #6-32 x 3/8" housing assembly
screws into the switch housing mounting plate as shown
in Figure 14.
B. Feed the upper plug connector through the center open-
ing of the upper switch housing. See Figure 14.
C. Align the keyhole slots in the upper switch housing with
the housing assembly screws installed in sub-step A.
D. Turn the upper switch housing counterclockwise until
the housing assembly screws are firmly situated in the
narrow end of the keyhole slots as shown in Figure 15.
Install the one remaining #6-32 x 3/8" housing assem-
bly screw into the third hole in the upper switch hous-
ing. Tighten all three screws firmly.
Caution: Make sure the upper switch housing is se-
curely attached to the switch housing mounting plate.
Failure to properly attach and tighten all three hous-
ing assembly screws could result in the switch hous-
ing and light fixture falling.
UPPER SWITCH
HOUSING
UPPER PLUG
CONNECTOR
LOWER SWITCH
HOUSING
ASSEMBLY
SCREW
LOWER PLUG
CONNECTOR
Step 10: Attaching The Lower Switch
Housing
Warning:
•
To avoid possible electrical shock disconnect power
by turning off the circuit breakers both to the outlet box
and to its associated wall switch location. If you cannot
lock the circuit breakers in the off position, securely
fasten a prominent warning device, such as a tag, to
the service panel.
•
All wiring must be in accordance with national and lo-
cal electrical codes and ANSI/NFPA 70. If you are un-
familiar with wiring, you should use a qualified electri-
cian.
A. Connect the upper plug connector from the motor to
the lower plug connector in the lower switch housing
assembly. See Figure 16.
Note: Both plug connectors are polarized and will only fit
together one way. Make sure that both connectors are prop-
erly aligned before connecting them together. Incorrect
connection could cause improper operation and damage
to the product.
B. Place the lower switch housing assembly over the up-
per switch housing. Align the side screw holes in the
upper and lower switch housings. Attach the lower
switch housing to the upper switch housing with three
#6-32 x 3/8" housing assembly screws. See Figure 16.
FIGURE 15
FIGURE 16