To replace the fi rst starter elbow with two 45° elbows,
refer to Figure 7.4. All other 90° elbows can be replaced
with two 45° elbows.
General Rules:
• SUBTRACT 3 ft. from the total H measurement for each
90° elbow installed horizontally.
• SUBTRACT 1-1/2 ft. from the total H measurement for
each 45° elbow installed horizontally.
• A maximum of three 90° elbows (or six 45° elbows)
may be used in any vent confi guration. Some elbows
may be installed horizontally. See Figure 7.9.
• Elbows may be placed back to back anywhere in the
system as long as the fi rst 90° elbow is a starter elbow
except as shown in Figure 7.4.
• When penetrating a combustible wall, a wall shield
fi restop must be installed on both sides.
• When penetrating a combustible ceiling, a ceiling
fi restop must be installed.
• Horizontal runs of vent do not require vertical rise;
horizontal runs may be level.
E. Vent Diagrams
Figure 7.3
One Elbow
V
1
H
1
1. Top Vent - Horizontal Termination - (continued)
V
1
min.
V
1
max.
H
1
max.
ft
m
ft
m
ft
m
0*
-
-
1.67
0.51
0.5
0.15
-
-
6
1.83
1
0.30
-
-
11
3.35
1.5
0.46
-
-
18
5.49
2
0.61
-
-
25
7.62
-
-
25
7.62
25
7.62
* You may install elbow directly on top of appliance.