3.Preparation before installation
The position relation among ceiling opening and hoisting screws (unit: mm)

Ceiling opening and the installation of hoisting screw

Treatment to ceiling

About the treatment of dismantling ceiling. In order to prevent the ceiling
from vibration, it is very important to strengthen the base of ceiling and insure
level of the previous ceiling.

*Cut and remove the base of the ceiling.

*Strengthen the cut surface of the ceiling base. Increase the ends and edges
of the ceiling to fix the ceiling base.

Install the hoisting screw
Use M8 or M10 hoisting screw (4, prepare on site) (When the height of
hoisting screw is more than 0.9m, you must use M10), their gaps refer to the
dimension of air conditioner, according to the original structure and the
following method to install.

Before hanging the indoor unit, please choose the installation position after
considering the connection pipes and connection wire inside the ceiling and

decide the out direction of the connection pipe.

*

When using the original ceiling, before hanging the unit, put the refrigerant

pipe, drain hose, indoor unit connection wire and wire control wire in the

position of the connection pipe and connection wire.

*

Confirm the dimension of indoor unit by using the attached installation

paper panel to make the indoor unit accord with the dimension of ceiling
opening and its position.(Use the attached 4 M5x12 screws to fix the

installation paper panelunder the indoor unit.)

Wood structure

(Instruction)

The dimension of the ceiling
opening with the mark of

*

can reach 910mm, but the
overlap part between ceiling

and decorative panel should
keep over 20mm.

950 (Decorative panel)

890

*(Ceiling opening)

840 (Indoor unit assembly)

780 (The distance betwe -en hoisting screws)

Refrigerant pipe

Hoisting screw

A direction

Over20

Ceiling

Hoisting angel iron

A

950 (Decorative panel)

890*(Ceiling opening)

840 (Indoor unit assembly)

780 (The distance betw

-een hoisting screws)

Installation procedure

Install indoor unit

Put up the frame wood on the beam
and mount the hoisting screws.

New cement panel

Use embedded parts and

foot screw, etc to mount.

(Knife type

embedded part)

(Louver type

embedded part)

(hoisting foot screw for

connection pipe)

24

Foot screw

Iron

Beam

Frame wood

Hoisting screw