Cwpac – Emerson Process Management Bristol ControlWave PAC User Manual
Page 5
October 2012
CWPAC
www.EmersonProcess.com/Remote
5
DO with Read-
Back (for
redundant I/O
systems only)
16 DI with local or remote automations. For more information, refer to
Product Data Sheet CWPAC:DIO
Universal Digital
Input Module and
Counter (UDI)
6 or 12 DI with local or remote automations. For more information, refer to
Product Data Sheet CWPAC:DIO
RTD
4 DI with local or remote automations. For more information, refer to
Product Data Sheet CWPAC:TEMP
Thermocouple
6 DI with local or remote automations. For more information, refer to
Product Data Sheet CWPAC:TEMP
Remote Terminal Blocks
AI and AO
Number of
Channels
AI, 4 channels; AO, 2 channels; TC, 8 channels
Dimensions
89.7 mm H x 45 mm W x 67.1 mm D (3.53 in. H x
1.77 in. W x 2.64 in. D)
DI and DO
Number of
Channels
8 channels
Dimensions
89.7 mm H x 55.9 mm W x 65.5 mm D (3.53 in. H x
2.2 in. W x 2.58 in. D)
Relay
99 mm H x 82.6 mm W x 94 mm D (3.9 in. H x 3.25
in. W x 3.7 in. D)
UDI
Number of
Channels
4 channels
Dimensions
89.7 mm H x 45 mm W x 67.1 mm D (3.53 in. H x
1.77 in. W x 2.64 in. D)
Cable Lengths
0.46 m (18 in.)
1.0 m (39 in.)
2.0 m (6.5 ft.)
4.0 m (13 ft.)
Power
Input Voltage
22.1 – 30.0 Vdc
Isolation
500 Vdc
Status Indication
Active, Fail, and Power OK
Physical
Dimensions
4 I/O Slot Chassis
Panel Mount
300.73 mm W by 177.03 mm H by 125.98 mm D
(11.84 in. W by 6.97 in. H by 4.96 in. D)
8 I/O Slot Chassis
Panel Mount or
19-inch Rack
Mount
481.58 mm W by 177.03 mm H by 125.98 mm D
(18.96 in. W by 6.97 in. H by 4.96 in. D)
Weight
4 I/O Slot Chassis
3.18 kg (7 lbs.)
8 I/O Slot Chassis
5.9 kg (13 lbs)
Wiring
Up to 14 American Wire Gauge (AWG)