beautypg.com

2 rs-485 and arc156 wiring considerations, 3 wiring for bacnet/arc156 network, Figure 9 bacnet/arc156 network port – Emerson SiteLink-12E User Manual

Page 13: Rs-485 and arc156 wiring considerations, Wiring for bacnet/arc156 network, Figure 9, Bacnet/arc156 network port, Bacnet

background image

Communication and Control Wiring

9

4.2

RS-485 and ARC156 Wiring Considerations

An RS-485 network is intended to be configured as a linear bus with daisy-chained connections (star

topologies are not recommended). Termination in RS-485 and ARC156 setups is usually applied to

both ends of the network (see 4.4.1 - Wiring Port S1 for RS-485 Network—Four-Wire).
Repeaters often are required when connecting 32 or more RS-485 or ARC156 devices or when using

ARC156 cable segments longer than 2000 feet. Refer to the BMS documentation for information on

when to use repeaters.
To reduce communication and data errors, terminate each end of the network with a resistor whose

value equals the network's characteristic impedance. Some third-party manufacturers provide a

built-in resistor that you enable or disable with a jumper. Make sure that only devices at the end of a

network have termination enabled.

EXAMPLE: If the network’s characteristic impedance is 120 Ohms, terminate the network by

placing a 120 Ohm resistor across the Net+ and Net- connectors of the Liebert SiteLink-E and a

120 Ohm resistor across the + and - connectors of the furthest third-party device.
Bias must be applied to each RS-485 network segment. To add bias to a network segment, put the

bias jumper in place on the DIAG485 that is in the middle of the segment. You can use additional

DIAG485s with the bias jumper removed to monitor network communication, but only one

DIAG485 may have the bias jumper in place.

4.3

Wiring for BACnet/ARC156 Network

Network Liebert SiteLink-E modules to other Liebert Site Scan modules using the ARCnet port. Set

the baud rate to 156 Kbps for all modules connected to the ARCnet156 network.

1. Be sure the module’s power is Off before beginning to connect wiring for the ARCnet port.
2. Check the network communication wiring for shorts and grounds.
3. Locate the BACnet terminal location in the upper left corner of the Liebert SiteLink-E module

(see Figure 1).

4. Connect the communication wiring to the control module’s screw terminals labeled Net +, Net -

and Shield using the labels near the ARCnet port as a guide. For details, see Figure 9..

Figure 9

BACnet/ARC156 Network port

NOTE
Use the same polarity throughout the network segment.

BT485

BACnet

®

Over ARCNET156 KBaud

Net +

Net -

Shield

ARCnet

Port

Connect Communication

Wiring to Terminals Using

Label Behind Port as

Guide

Wiring

Terminals

This manual is related to the following products: