Dimensional Data

9

Figure 4

Cabinet and floor planning dimensions, upflow models—CW026-CW084

Model

No. of

Blowers

Dimensional Data, inches (mm)

Net Weight,

lb (kg)

A

B

C

D

E

F

G

H

J

K

L

M

CW026

1

50

(1270)

48

(1219)

46

(1168)

44

(1118)

3

(76)

5

(127)

18

(457)

15-7/8

(403)

18-5/8

(473)

2-3/16

(55)

17-3/8

(454)

760

(345)

CW038

1

50

(1270)

48

(1219)

46

(1168)

68

(1727)

3

(76)

5

(127)

18

(457)

15-7/8

(403)

18-5/8

(473)

2-3/16

(55)

17-3/8

(454)

795

(361)

CW041

1

50

(1270)

48

(1219)

46

(1168)

44

(1118)

3

(76)

5

(127)

18

(457)

15-7/8

(403)

18-5/8

(473)

2-3/16

(55)

17-3/8

(454)

855

(388)

CW051

2

74

(1880)

72

(1829)

70

(1778)

44

(1118)

3

(76)

4

(102)

20

(508)

15-7/8

(403)

14-5/8

(371)

2-3/16

(55)

20-3/8

(517)

11-1/4

(286)

1090

(494)

CW060

2

74

(1880)

72

(1829)

70

(1778)

68

(1727)

3

(76)

4

(102)

20

(508)

15-7/8

(403)

14-5/8

(371)

2-3/16

(55)

20-3/8

(517)

11-1/4

(286)

1155

(524)

CW076

2

99

(2515)

97

(2464)

95

(2413)

86

(2184)

6-1/2

(165)

5

(127)

18

(457)

15-7/8

(403)

18-5/8

(473)

3 1/4

(82)

20-5/8

(524)

12-5/8

(321)

1320

(599)

CW084

2

99

(2515)

97

(2464)

95

(2413)

86

(2184)

6-1/2

(165)

5

(127)

18

(457)

15-7/8

(403)

18-5/8

(473)

3 1/4

(82)

20-5/8

(524)

12-5/8

(321)

1420

(644)

Shaded areas indicate
a recommended
clearance of 36" (914mm)
for component access
and filter removal.

Models With Rear Return

Unit Dimensional Data

B

Un

it B

ase

1"

(25.4mm)

72"

(1829mm)

1"

(25.4mm)

1"

(25.4mm)

A

Overall

Dimension

Projection Of

Display Bezel

3/4" (19mm)

Floor Cutout Dimensions

Models With Bottom Return

Flo

or L

eve

l

Ai

r R

etu

rn

O

pe

nin

g

A return air grille
may be ordered in
place of the duct
flange. See specification
sheet for option supplied.

Air grille may
be supplied on
units with front
or rear return air

Duct Flanges on 2 Blowers

22"

(55

9m

m)

5-1/2"

(139.7mm)

G

Air Return

Opening

DPN001661
Rev. 0

F

E

D

C

B

Duct Flanges on One Blower

Note: Flanges
provided on
blower(s)
outlet for
supply air
ducting.

1" (25.4mm) Flange
for Plenum
Connection

1-1

/8"

(28

.6m

m)

35-5/8"

(905mm)

Overall

Dimensio

n

35"

(889mm

)

Front of Unit

33

"

(83

8m

m)

Unit Base

Front of Unit

H

H

J

J

J

K

M

K

L

Air Return

Opening