Location of the appliance

This appliance must not be installed in a bed-sitting room

of volume less than 20m³

or in a bathroom, shower room

or garage. It is essential that the appliance is positioned

as stated below (see fig.1) i.e. shelves, wall cabinets

and cooker hoods must be fitted a minimum of 787mm

directly above the top of the hotplate and 400mm above

the hotplate when fitted in line with the outside of the

appliance. If the units are intended to be fitted adjacent

to the appliance but less than 400mm above the hotplate,

then a minimum space of 100mm must be maintained

between the sides of the unit and the appliance. Curtains

must not be fitted immediately behind the appliance or

within 150mm of the sides of the hotplate. If fitted next

to or between two base units a minimum space of 2mm

must be left between each unit and the side of the

appliance. The levelling feet fitted to the appliance will

achieve a nominal height to hotplate trims of 900mm

+20mm.

L.P.G. cookers MUST NOT be installed below ground

level, i.e. in a basement, or aboard any boat, yacht or

other vessel.

Positioning the Cooker

Caution: Some soft or badly fitted floor coverings can be

damaged when the cooker is moved across their surface

for cleaning. It is advisable to ensure that the floor covering

in the area below the cooker is either securely fixed so as

not to ruck up when the cooker is moved or, if preferred,

removed.

Important Safety Requirements

This appliance must be installed in accordance with the

Gas Safety (Installation and Use) Regulations (current

addition) and the I.E.E. Wiring Regulations. Detailed

recommendations are contained in the following British

Standard Codes of Practice - B.S. 6172, B.S. 5440: Part

2 and B.S. 6891: Current Editions.

Provision for Ventilation

The room containing the cooker should have an air supply

in accordance with B.S. 5440: Part 2: Current Editions.

The following requirements for ventilation must be met.

The cooker should not be installed in a bed sitting room

with a volume of less than 20m

3

, if it is installed in a

room of volume less 5m

3

an air vent of effective area of

110cm

2

is required; if it is installed in a room of volume

between 5m

3

and 10m

3

, an air vent of effective area 50cm

2

is required, while if the volume exceeds 11m

3

no air vent

is required. However, if the room has a door which opens

directly to the outside, no air vent is required even when

the volume is between 5m

3

and 11m

3

.

If there are other fuel burning appliances in the same

room, B.S. 5440: Part. 2: Current Editions should be

consulted to determine the requisite air vent

requirements.