BACnet Variables

Envision Console Controls

3:9

BO5 Output

[Read, shows the BO5 (electric heat) output value,

Inactive=Off, Active=On]

3:10

BO9 Output

[Read, shows the BO9 output value, Inactive=Off,

Active=On]

Multistate Input (Type 13)

13:1

Effective Occupancy

[Read, show the prevailing occupancy status of

the heatpump1=Occupied, 2=Unoccupied,

3=Bypass, 255=Invalid]

13:2

Mode Status

[Read, Shows unit status as Auto or Shutdown,

1=Auto, 7=Shutdown]

Multistate Output (Type 14)

14:1

Occupancy Command

[Write, Control the occupancy mode of the

heatpump. 1=Occupied, 2=Unoccupied, 3=Bypass,

255=Invalid]

14:2

Fan Command (G)

[Write, allows a network command equivalent of

a thermostatic ‘G’ call]

14:3

Compressor Cmd (Y1)

[Write, allows a network command equivalent of a

thermostatic ‘Y1’ call]

14:4

Compressor Cmd (Y2)

[Write, allows a network command equivalent of a

thermostatic ‘Y2’ call]

14:5

Reversing Vlv Cmd (O)

[Write, allows a network command equivalent of a

thermostatic ‘O’ call]

14:6

Emergency Overide

[Write, provide rapid shutdown of the heatpump

for fire,etc. 1=Normal, 5=Shutdown]

14:7

Alarm Reset

[Write, Reset lock-out ‘manual reset’ alarms. Alarm

conditions must be cleared before a reset can

succeed. This variable should be commanded

‘On’ for 20 seconds, then returned to the ‘Off’

condition. 1=Off, 2=On]

14:8

Emergency Heat BO5

[Write, allows a network command for emergency

heat, also allows the network to stop automatic

emergency heat.]

14:9

BO9

[Write, allow network control of spare output BO9.

1 = Off, 2=On.]

14:10

Dehum Cmd