Dual-Compressor Module

Installation

Figure 8 Optional Customer-Installed High Temperature Fan Control System

Power Supply

24VDC

PLC

Or

Temperature

Control

SZO44

Compressor

Module

0-10VDC Fan Speed Signal
0.9V = Off; 1.3V = 50%; 10V = 100%

Temperature Sensor

• Compressor requirements: 1.2 to 2 GPM (4.5-755 LPM) flow rate
• Operating temperature range, standard: 190° to 210°F (88°- 99°C)
• Thermal oil bypass valve, standard setting: 200°F (93°C)
• Thermal bypass valve operation (valve’s purpose is to provide discharge temperature control)
• Oil flow on valve is A to B when the unit is cold and A to C when the heat rises (see

Figure 9).

Figure 9 Oil Cooling and Thermal Valve

A

B

C

Oil Cooler

Return

to Compressor

1st-Stage Separator