beautypg.com

Gas line connection and testing, Initial installation, Never use an open flame for leak testing – Enviro EG28 DV User Manual

Page 22

background image

Initial Installation

G

AS

L

INE

C

ONNECTION

AND

T

ESTING

:

WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to this

appliance.
GAS LINE CONNECTION
• This stove is equipped with a certified flexible pipe located on the right side of the unit terminating in a 3⁄8” male

NPT fitting. Consult your local authorities codes or the CAN/CGA B 149 (1 or 2) installation code in Canada, or

in the USA gas installations follow either local codes or the current edition of the National Fuel Gas Code ANSI

Z223.1.

• The efficiency rating of this appliance is a product thermal efficiency rating determined under continuous

operating conditions and was determined independently of any installed system.

The appliance and its shutoff valves must be disconnected

from the gas supply piping system during any pressure

testing where the pressure exceeds 1⁄2 PSIG (3.45 KPa)

or damage will occur to the valve.
The appliance must be isolated from the gas supply

piping system by closing its individual manual shutoff

valve during any pressure testing of the gas supply

piping system at test pressures equal to or less than 1⁄2

psig (3.45 KPa).

Always check for gas leaks with a soap

and water solution after completing the

required pressure test.

TO TEST VALVE PRESSURES
The pressure taps are located on the left side of the valve
• Turn set screw 1 turn counter clockwise to loosen,
• Place

5

/

16

” (8 mm) I.D. hose over pressure tap system.

• Check pressures using a manometer.
• When finished, release pressure, remove hose & tighten set screw.

Natural Gas

Propane

Main Orifice

#43 DMS

#53 DMS

Manifold Pressure

3.8” W.C. (0.95 KPa)

11.0” W.C. (2.74 KPa)

Min. Manifold Pressure

1.1” W.C. (0.27 KPa)

2.7” W.C. (0.67 KPa)

Max Supply Pressure

7.0” W.C. (1.74 KPa)

12.0” W.C. (2.98 KPa)

Min. Supply Pressure

5.0” W.C. (1.25 KPa)

11.5” W.C. (2.86 KPa)

Max BTU/hr Input 26,500 BTU/hr (7.87 KW)

26,500 BTU/hr (7.87 KW)

Min. BTU/hr Input

13,500 BTU/hr (3.9 KW)

13,500 BTU/hr (3.9 KW)

NEVER USE AN OPEN FLAME FOR LEAK TESTING.

O

L I

T

P

TP

TH

TP

TH

IN

OU

T

H

I

LO

N

OF

O

F

LI

P

T O

��������

�������� ���

�����

�������� ���

������

����

����� ����������

�����

��� �������

����

Figure 30: Fully Labeled Gas Valve.

Table 6: Pressure and BTU Information.

22

This manual is related to the following products: