Diagnostics

Page 32 of 36

ProSoft Technology, Inc.

June 10, 2015

2. I/O LED (Right):

a. Green: USB enabled

b. LED not on: No power

i.

Connect USB to PC first, then to I/O Expansion Module.

ii.

Verify unit is powered on, Power LED (left) should be red.

iii.

Verify the PC is on.

3. Unable to Read/Write Modbus Values

a. Verify that the Modbus slave ID is the Module ID + 1

Example: If the Module ID is 0, the Modbus slave ID will be 1

b. Select MSB first when applicable when setting up Modbus Master device.

c. Verify Modbus RS485 wiring (3-wire).

d. Verify baud rate, data bits, parity, and stop bits (9600 / 8 / None / 1).

e. Refer to Modbus Mapping (page 27).

i.

Verify the Modbus function code.

ii.

Verify the Modbus register address.

iii.

Verify the data type (integer/float, 16/32 bit).

iv.

Verify if address has read/write or only read function capabilities.