4 0-10 v i/o module - modbus mapping table, Modbus mapping – ProSoft Technology BM-1000-PM1K User Manual
Page 29

Modbus Mapping
ProSoft Technology, Inc.
Page 29 of 36
June 10, 2015
3001
Analog Input 1 Volts /1000
Read
UINT 16
0..10,000
3002
Analog Input 2 Volts /1000
Read
UINT 16
0..10,000
3003
Analog Input 1 Raw Split-Hi
3004
Analog Input 1 Raw Split-Lo
3005
Analog Input 2 Raw Split-Hi
3006
Analog Input 2 Raw Split-Lo
3007
Analog Input 1 Volts Split-Hi
3008
Analog Input 1 Volts Split-Lo
3009
Analog Input 2 Volts Split-Hi
3010
Analog Input 2 Volts Split-Lo
3011
Analog Output 1 Raw
Read/Write
UINT 16
0..65,535
3012
Analog Output 2 Raw
Read/Write
UINT 16
0..65,535
3013
Analog Output 1 Volts /1000, % /100
Read/Write
UINT 16
0..10,000
3014
Analog Output 2 Volts /1000, % /100
Read/Write
UINT 16
0..10,000
3015
Analog Output 1 Volts Split-Hi
3016
Analog Output 1 Volts Split-Lo
3017
Analog Output 2 Volts Split-Hi
3018
Analog Output 2 Volts Split-Lo
3019
Analog Output 1 % Split-Hi
3020
Analog Output 1 % Split-Lo
3021
Analog Output 2 % Split-Hi
3022
Analog Output 2 % Split-Lo
5001
Analog Input 1 Raw
Read
UINT 32
0..8,388,607
5002
Analog Input 2 Raw
Read
UINT 32
0..8,388,607
7001
Analog Input 1 Volts
Read
IEE FLOAT
0.0..10.0
7002
Analog Input 2 Volts
Read
IEE FLOAT
0.0..10.0
7003
Analog Output 1 Raw
Read/Write
IEE FLOAT
0.0..65,535.0
7004
Analog Output 2 Raw
Read/Write
IEE FLOAT
0.0..65,535.0
7005
Analog Output 1 Volts
Read/Write
IEE FLOAT
0.0..10.0
7006
Analog Output 2 Volts
Read/Write
IEE FLOAT
0.0..10.0
7007
Analog Output 1 %
Read/Write
IEE FLOAT
0.0..100.0
7008
Analog Output 2 %
Read/Write
IEE FLOAT
0.0..100.0
0..8,388,607
UINT 32
0..8,388,607
UINT 32
Read
Read
IEE FLOAT
0.0..10.0
IEE FLOAT
0.0..100.0
IEE FLOAT
0.0..100.0
IEE FLOAT
0.0..10.0
IEE FLOAT
0.0..10.0
IEE FLOAT
0.0..10.0
Read/Write
Read
Read
Read/Write
Read/Write
Read/Write
6.4
0-10 V I/O Module - Modbus Mapping Table