3specifications, 1 hardware and system, 2 safety and compliance – ProSoft Technology BM-1000-PM1K User Manual
Page 11

Specifications
ProSoft Technology, Inc.
Page 11 of 36
June 10, 2015
3
Specifications
3.1
Hardware and System
HARDWARE & SYSTEM
Unique Features
Works with Any Modbus RS485 Master Device
No Software Configuration Required
Single Point Power Termination
Maximum Network Capacity*
System can support up to sixteen (16) Digital Modules max
System can support up to eight (8) 0-10 V Modules max
System can support up to five (5) 4-20 mA Modules max
When adding more than five (5) I/O Modules and creating different
I/O Module combinations, please determine maximum allowable I/O
Module combination per system by utilizing the power budget
calculator.
Power Budget Calculator
Data Encoding Method
MSB First
I/O Module Slave ID Selection
16-Position Rotary Switch (+1 for Modbus Slave ID)
DIN Rail Mounting Compatibility
35 mm x 7.5 mm DIN Rail
DataRail™ (Included w/ Kit)
6.1" / 156 mm - Supports Up to Exp. + 5x I/O Modules
Auto-Detection of Modules
Yes, via DataRail at Power-Up
DataRail Mounting Hardware
4-Claw Attachment to 35 mm DIN Rail with End Terminal Bracket
Built-In Mounting Hardware
Spring-Loaded Clip-On System
Wire Gauge
Solid / Stranded (AWG) 28-12 Gauge
Wire Rating
UL: 300 V RMS, 80 °C and 300 V, 105 °C
CSA: 300 V RMS, 105 °C
Warranty
2-Year Limited
3.2
Safety and Compliance
SAFETY & COMPLIANCE
RADIO
Operational Temperature
-40 °C to 85 °C / -40 °F to 185 °F
Ambient Temperature
-20 °C to 85 °C / -4 °F to 185 °F
Humidity
0 to 99 %, Non-condensing
Degree of Protection / Housing Type
IP20 / Plastic
Hazardous Locations Classifications
Class I; Division 2 (Zone 2), Pending