ProSoft Technology 3170-MBS User Manual
Page 25

3170-MBS ♦ Flex Platform
Status Information
Modbus Slave Interface Module
User Manual
ProSoft Technology, Inc.
Page 25 of 55
October 27, 2010
5.2
Module Status Words
Slot Status: indicates the general health of the installed I/O module
Number of Words: either 3 or 15 words indeterminate if slot is empty.
Number of Read Words: the number of words which are to be read from the
I/O module, indeterminate if slot is empty.
Address
Bit:
15 14
13 12
11 10
9
8
7
6
5
4
3
2
1
0 40122
Status
Total
Words
Read
Words
Type
Identity
to 40129
Type ID: a byte when combined with the Number of Words and Number of
Read Words form the Module ID which uniquely identifies a specific module
function, series and revision, indeterminate if slot is empty. Note that all of
bits 0 through 12 should be used in identifying a module.
Bit 15
1 = No answer, empty slot or dead module
Bit 14
1 = Either positive edge of bit 15 or bit 13 detected
Bit 13
1 = Bit failure, bad data on SerBus
Bit 12
1 = Number of words is 15, = 0 number of words is 3
Bits 11 to 8
Value = number of read words
Bits 7 to 0 Value = Type ID