MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform
Module Setup
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 65 of 225
July 8, 2011
6 Double click the slave icon to view the Slave Device properties.
In particular, note the following settings:
o
Automatic PROFIBUS Address Assignment:
ProSoft Configuration Builder automatically assigns a PROFIBUS address
to each new slave. The address assignment begins at address 3, and is
incremented by 1 for each new slave added to the network. You can
change the address in the Common tab of the Slave Properties dialog
box.
o
Automatic Input/Output Address Assignment:
For each new slave added to the PROFIBUS network, ProSoft
Configuration Builder automatically converts the input/output byte
addresses to word input/output addresses for the State RAM in the
processor.
7 Repeat steps 2 through 6 for all slaves you intend to place on the network.
8 When you are finished adding slaves, open the P
ROJECT
menu and choose
E
XIT
to return to the Master Setup dialog box.