Mailbox Messaging
MVI69-PDPMV1 ♦ CompactLogix or MicroLogix Platform
User Manual
PROFIBUS DPV1 Master
Page 112 of 225
ProSoft Technology, Inc.
July 8, 2011
Slave Address
Address of the slave to which a connection shall be established. Range: 0 to 126
Max. Data Length
The slave’s maximum data length in bytes (reported by the slave in DP
Initiate.res).
Min. Slave Send Timeout
The minimum slave timeout value supported by the slave (in multiples of 10ms).
Error Decode, Error Code 1 & 2
If ‘Fault Information’ equals 0010h, additional information according to the DPV1
specification can be found in this portion of the message.
Fault Information
If ‘Invalid Other’ is returned in the Message Information word in the header of the
response, information about the fault can be found here.
Extended Fault Information
If ‘Fault Information’ equals 000Ah or 000Bh, additional information of the error
can be found here. For more information, see “Class 2-Related Errors”.
"Fault Information"
"Extended Fault Information" Contents
0001h
Address out of range
-
000Ah
Failed to execute request
Refer to Class 2-Related Errors.
000Bh
Remote station failure
0010h
Remote station DPV1 failure
Function_Number
00FFh
Module offline (not initialized or no
valid database)
-
Send Timeout
Defines the control time (timebase 10ms) for the supervision of the connection
between the
slave and the master. Range 6 to 65535 (equals 60 to 655350ms). Default is
1000ms.