ProSoft Technology MVI69E-MBTCP User Manual
Page 135

MVI69E-MBTCP ♦ CompactLogix Platform
Reference
Modbus TCP/IP Enhanced Communication Module
User Manual
ProSoft Technology, Inc.
Page 135 of 150
May 20, 2015
7.4.9 Get General Module Status Data Block (9250)
This block requests general module status.
Block 9250: Request from Processor to Module
Offset
Description
0
Block ID 9250 to request the general module status response block
Block 9250: Response from Module to Processor
Offset
Description
0
Block ID 9250 requested by processor
1
The next read request block identification code
2
Program Scan Count: this value is incremented each time a complete program cycle
occurs in the module.
3 to 4
Product Code: these two registers contain the product code of "MB6E" for the
MVI69E-MBTCP module.
5 to 6
Product Version: these two registers contain the product version for the current
running software
7 to 8
Operating System: these two registers contain the month and year values for the
program operating system.
9 to 10
Run Number: these two registers contain the run number value for the currently
running software.
11
Read Block Count: total number of read blocks transferred from the module to the
processor.
12
Write Block Count: total number of write blocks transferred from the processor to the
module.
13
Parse Block Count: total number of blocks successfully parsed that were received
from the processor.
14
Event Command Block Count: total number of Event Command blocks received
from the processor.
15
Command Block Count: total number of command blocks received from the
processor.
16
Error Block Count: Total number of block errors recognized by the module.
17
Client 0 command execution word: each bit in this word enables/disables the
commands for client 0. If the bit is set, the command executes. If the bit is clear, the
command is disabled
18 to 36
Client 1 to client 19 command execution words
37 to 38
Event Sequence Ready: bit mapped -1 bit for each client 0-19
Bit=0: No event sequence status data ready
Bit=1: Event seq. status data ready
39
Encapsulated Modbus TCP/IP request count: this counter increments each time the
module receives an Encapsulated Modbus TCP/IP (Service Port 2000) request from
a remote Modbus TCP/IP client,
40
Encapsulated Modbus TCP/IP response count: this counter increments each time
an Encapsulated Modbus TCP/IP (Service Port 2000) response is sent back to a