19

Display Indications

Message

Cause

Reference to exeeding the limit of a measurement value

Probe

Interruption / exchange probe(S) - earth probe (ES) (at 4 pole measurement)
Interruption / exchange probe (S) - earth (E) (at 3 pole measurement)
Interruption auxillary earth (H) - earth (E) (at 2 pole measurement)

Limit

IM

Interruption auxillary earth (H) - earth (E) (at 4/3 pole measurement)

Unoise

External voltage has exceeded admissible value,
Measurement values do not longer correspond to the specifications!

Limit

RH

Measurement value RH > 50 k

Ω

or RH > 1000 RE
measurement values do not longer correspond to specifications

Limit

RS

Measurement value probe resistance (RS) > 50 k

Ω

or probe resistance (RS) > 10000 x RE
Measurement values do not longer correspond to specifications!

Limit

RE

Measurement value earth resistance (RE) > 2 k

Ω (at 4/3 pole measurement)

Displayed measurement values for RH, RS are then RH+RE,RS+RE !

Limit

Measurement value R > 2k

Ω (at 2 pole measurement)

Battery-
Symbol

Batteries are nearly empty. must be changed.
Measurement values do not longer correspond to specifications!

Batt-Symbol
is
blinking

Batteries are complete empty. measurement no longer possible!