beautypg.com

Epen, Re r – Amprobe Telaris-Earth-Test Earth-Resistance-Tester User Manual

Page 15

background image

13

Earth Resistance Measurement (two-wire method)

The two-wire method consists of measuring the resistance between the earth under test and
a known earth. For this purpose, the PEN conductor of a TN system can be used, for example.
The resistance of the known earth connection has to be subtracted from the measurement
result. This measurement is also feasible in a densely populated or in sealed areas where rods
and auxiliary earth connections may not be installed.

Figure 3: two-wire method

1) Connect

earth

to

be tested with socket (E) and known earth with socket (H), also refer

to fig. 3

2)

Turn the rotary switch (13) to the "2 pole" position.

3)

Set contact voltage (11) by using key “UL“.

4)

If required choose manual frequency selection by using key “auto/man” (16), and
select test frequency with key “f1/f2” (12).

5)

Press key "Start" (14).

6)

Read the measurement result from the display.

• Also refer to display indication

• After the measurement, selection can be made between display of earth resistance or

measurement current (IM) by using key “Display“(8), depending on the measurement result.

• Possibility to measure conventional resistance by using the grounding resistance

measurement range. For this purpose, connect test leads E and H to the DUT. Test current
is fed via lines E and H, measurement voltage is measured via E and H.

E

PEN

RE

R

PEN

PAEB30872261:Layout 1 12.12.2007 12:06 Uhr Seite 13