beautypg.com

Amprobe DM-II-PLUS Power-Quality-Recorder User Manual

Page 20

background image

18

Symbols

Description

Advised Settings

CO-GENERATION

This instrument can record co-generation (the
equipment under test generates energy as well as
absorbing it).
ON = Record the powers and energies both ab-
sorbed and generated. If this flag is enabled, only
38 parameters can be selected.
OFF = Record only the powers and energies
absorbed.

Pt, P1, P2, P3,

P12, P32

Values of the active power (total, of phase 1,
phase 2 and phase 3) (only for 3PH3W) value of
the power measured by the Wattmeter 1-2 and
3-2 respectively

Single phase: P1
3 wires: Pt
4 wires: Pt, P1, P2,
P3

Qti, Q1i, Q2i, Q3i,

Q12i, Q32i

Values of the inductive reactive power (total, of
phase 1, phase 2, phase 3) (only for 3PH3W) value
of the reactive inductive power measured by the
VAR meters 1-2 and 3-2 respectively

Single phase: Q1i
Q1c
3 wires: Qti Qtc
4 wires: Qti Q1i
Q2i, Q3iQtc Q1c
Q2c, Q3c

Qtc, Q1c, Q2c,Q3c,

Q12c, Q32c

Values of the capacitive reactive power (total,
phase 1, phase 2, and phase 3)
(only for 3PH3W) value of the reactive capacitive
power measured by the VA meters 1-2 and 3-2
respectively

St, S1, S2, S3,S12,

S32

Values of the apparent power (total, phase 1,
phase 2,and phase 3)
(only for 3PH3W) value of the power measured
by the VA meters 1-2 and 3-2 respectively

Single phase: S1
3 wires: St
4 wires: St, S1, S2,
S3

Pft, Pf1, Pf2, Pf3

Values of the power factors (total, of phase 1,
phase 2 and phase 3 respectively)

Single phase: Pf1
dPf1
3 wires: Pft dPft
4 wires: Pft Pf1 Pf2
Pf3dPft dPf1 dPf2
dPf3

dpft, dpf1, dpf2,
dpf3

Values of the cosϕ (total, of phase 1, phase 2 and

phase 3 respectively)

Eat, Ea1, Ea2, Ea3

Values of the active energy (total, of phase 1,
phase 2, phase 3)

Single phase: Ea1
3 wires: Eat
4 wires: Eat Ea1 Ea2
Ea3

Erit, Eri1, Eri2, Eri3

Values of the inductive reactive energy (total, of
phase 1, phase 2 and phase 3)

Single phase: Eri1
Erc1
3 wires: Erit Erct
4 wires: Erit Eri1
Eri2 Eri3Erct Erc1
Erc2 Erc3

Erct, Erc1, Erc2, Erc3

Values of the capacitive reactive energy (total, of
phase 1, phase 2, phase 3)

Est, Es1, Es2, Es3

Values of the Apparent Energy (total, of phase 1,
phase 2, phase 3)

Single phase: Es1
3 wires: Est
4 wires: Est Es1 Es2
Es3

Analyzer Memory (Refer to fig.25)

It shows the current instrument memory, the size of the memorized data and space available
for future recordings.

Push MENU, select ANALYZER MEMORY using Up and Down keys.
A list of recordings and samples will be displayed with each START – STOP date in the