This measuring method, based on resistance ratios, gives a dimensionless result,
independent on a series of factors such us equipment size, temperature or environmental
conditions.

Insulator status

60/30 sec ratio

Polarization index

10/1 min ratio

dangerous

───

less than 1

questionable

1.0

ч 1.25

1.0

ч 2

good

1.4

ч 1.6

2

ч 4

excellent more

than

1.6 more

than

4

Tab. 1: Insulator status as revealed by the polarization index.

The measurement of the polarization index of a dielectric can be taken by manufacturers
of electrical equipment to test, for example, materials to be used for the production of
supports for conductors, components and devices, insulation of motor coils.

KEY OPERATION

Ш

Ч

Reach the memory cell P20. PI is displayed.


SeT

The V2 parameter indicator is flashing.

Ш

Ч

Set the desired V2 voltage value (test voltage) between 100 and 5000V. The
top secondary display will show the value you are setting.


SeT

The T2 parameter indicator is flashing.


SeT

Leave the programming phase. The flashing measuring mode TIMER
advises that you can save the settings.


SavE

Save the parameters in the location previously selected (if requested).


StarT

The message “go?” is displayed.


StarT

The measurement is started.



• The test can be interrupted at any time (provided that at least 75 seconds have passed

from starting).

• At the end of the measurement the PI value is displayed. Press MODE to display the

last resistance value measured.

• Press SAVE to store the measured values.

• It’s possible to recall the measured values. Press SET/EXIT to run over the PI values,

the resistance values and the measuring parameters.





-18-