Amprobe ACD-30P Clamp-On-Power-Meters User Manual
Page 14

13
Range
frequency
Accuracy
1) 2)
40.00A, 400.0A, 1000A
50 Hz / 60 Hz
± (0.5% rdg + 5d)
40.00A, 400.0A
45 to 50 Hz, 60 to 500 Hz
± (2.0% rdg + 5d)
1000A
± (2.5% rdg + 5d)
40.00A, 400.0A
500 Hz to 3.1 kHz
± (2.5% rdg + 5d)
1000A
± (3.0% rdg + 5d)
ACA AutoVA
TM
Threshold: 1A AC (40hz ~ 500hz only) nominal
Crest factor:
40.00A & 400.0A:
< 2.5 : 1 at full scale; < 5.0 : 1 at half scale
1000A:
< 1.4 : 1 at full scale; < 2.8 : 1 at half scale
1)
induced error from adjacent current-carrying conductor: < 0.06A/A
2)
Specified accuracy is from 1% rdg to 100% rdg of range and for measurements made at
the jaw center. when the conductor is not positioned at the jaw center, position errors
introduced are:
Add + 1% rdg to specified accuracy for measurements made wiThin jaw marking lines
(away from jaw opening)
Add + 4% rdg to specified accuracy for measurements made BeYonD jaw marking lines
(toward jaws opening)
temperature
Range
Accuracy
-50°C to -20°C
± (2.0% rdg + 6°C)
-20°C to 300°C
± (2.0% rdg + 3°C)
-58°f to -4°f
± (2.0% rdg + 12°f)
-4°f to 572°f
± (2.0% rdg + 6°f)
Type-K thermocouple range & accuracy not included
frequency
Range
5.00 hz to 500.0 hz
Accuracy:
± (0.5% rdg +4d
Range
Sensitivity (Sine RMS)
40A
> 4A
400A
> 40A
1000A
> 400A
600V
> 30V
tHD% rdg-f
1)
(ACD-41PQ only)