Checking functional members – Subaru Robin SGX3500 User Manual
Page 20

- 18 -
6. CHECKING FUNCTIONAL MEMBERS
6-1 RECEPTACLES
Using a circuit tester, check continuity between
the two terminals at the rear of the receptacles
while the receptacle is mounted on the control
panel.
When continuity is found between the output
terminals of the receptacle with a wire connected
across these terminals, the receptacle is normal.
When the wire is removed and no continuity is
found between these terminals, the receptacles
are also normal.
6-2 CIRCUIT BREAKER
Check continuity between each of two
terminals at the rear of the circuit breaker
while it is mounted on the control panel.
Normally, there is continuity between each of
the two when the circuit breaker is on while
there is no continuity when the circuit breaker
is off.
CIRCUIT TESTER
(Continuity test)
PUSH Type
LEVER Type
AC CIRCUI BREAKER (Type 1)
AC CIRCUI BREAKER (Type 2)
Max voltage
AC CIRCUIT BREAKER
Frequency
Rated output
SGX5000
SGX7500
60Hz
SGX3500
3200VA
6700VA
4500VA
Rated fault current
18.75A
25A
37.5A
250V
250V
250V
SGX7500
6700VA
125V
20A
60Hz
Rated fault current
AC CIRCUIT BREAKER
Frequency
Rated output
Rated voltage