5-2 AC OUTPUT MEASURING
Use a circuit above for measuring AC output.
A hot plate or lamp with a power factor of 1.0
may be used as a load. Adjust the load and rpm.
and check that the voltage range is as specified
in the following table at the rated amperage and
rated rpm.
5-3 MEASURING INSULATION RESISTANCE
Use a megger tester to check the insulation
resistance. Remove the control panel, and
disconnect the connector of GREEN lead for
ground. Connect a megger tester to one of
receptacle output terminals and the ground
terminal, then measure the insulation resistance.
Rated voltage
240V-60Hz
SGX3500
239-249
SGX5000
239-249
SGX7500
239-249
V