Subaru Robin RGX3600 User Manual
Page 22

– 19 –
4-2 AC OUTPUT MEASURING
SWITCH
LOAD
TO AC RECEPTACLE
F
A
~
V
~
Use a circuit above for measuring AC output. A hot plate or lamp with a power factor of 1.0 may be used as a
load. Adjust the load and rpm, and check that the voltage range is as specified in the following table at the
rated amperage and rated rpm.
4-3 DC OUTPUT MEASURING
To DC Terminal
SW
Load
Measurement of DC output is executed with the switch turned ON while the current is regulated at 8.3A by
adjusting the load to the generator. If the voltage is within the range from 6V to 14V, the voltage output is
normal.
NOTE : If a battery is connected as a load to the generator, the DC output voltage will increase by
approximately 1 to 2 V.
Therefore, carefully observe the electrolyte level and do not overcharge the battery.
Model
Specification
50Hz-220V,230V
60Hz-120/240V
V
oltage range
RGX2900
RGX3600
RGX4800
226-259
113-130
207-238
50Hz-240V
226-259