Make sure DucTester 350 is showing on the
Home screen.

If not, tap the fan picture, then

Tap

, tap DucTester 350, then select the

range that you have installed.

Tap on [Channel B] to change the type of result
or units. Select based on “Get the results you
need” on page 4.

Tap [Settings] then [Time averaging] and
select 5 seconds.

Tap [Settings] then .

Make sure the [Default @ Pressure] is 80, 160,
or 250 Pa, depending on the test pressure you
need. Make sure “n” value is set to 0.60 for Ducts.

Tap to return to the Home screen.

Step 1:

Prepare ducts and house

Seal all supply and return grills/registers, including

any exterior air inlets, with Grill Mask or tape.

Open all interior doors leading to rooms containing

a supply or return register, and open an exterior door

or window.

Shut off all HVAC (A/C, furnaces).

Page 2 of 4

Step 2:

Connect to ducts

Turn off air-handler

and remove all filters.

Attach Flex Duct to

register.

Install Range Plug 74 to start,

as most systems can be tested

on this Range Configuration.

3

7 11 18

29 47 74

Tap

on the gauge and select

the range to match your fan, whenever

a Range Plug is changed.

Prepare the gauge

Use smaller Range number for tighter ducts, and

larger number for leakier ducts.