Tubing Accessory Kit

35 ft (10 m) of blue, red, yellow and green 1/4 inch

(12mm) outside diameter tubing. Static Pressure

Probe, 4 inch (100 mm) x 1/8 inch (6 mm) outside

diameter metal probe, 2 T and 2 male-to-male con-

nectors. Red L for duct leakage to outdoors test.

Part #: TU119

Flow Hood

24 x 24 inches

(61 x 61 cm)

Part #: PP105

Page 8 of 8

Optional accessories

12.5ft (3.8m)

Flex Duct for

DucTester

Part #: DU161

Flange

to connect

Flex Duct to

register

Part #: DU157

Verification

Plate

Part #: DU159

Deluxe Cordura Toolbag with
Shoulder Strap

Part #: TL118

Grill Mask 12in x 216ft,

12in perfs,

Hi-stick White,

Single Roll

Part #: GR116

Part #: GR117

(for case of 3)

Umbilical for

DucTester

fans, 7ft (2 m)

Part #: DM240

Optional DU159 Verification

Plate shown.

Tape the optional flow

Verification Plate to the

Flange and attach the

red tube.

Attach the Flex Duct to the

exhaust side of the fan

to pressurize the Flex Duct.

Stretch the Flex Duct to

it’s full length.

Set the DM-2 to measure

“Flow” in “CFM @25 Pa”.

Adjust the speed until

“PrA” reads close to 25 Pa.

Read the Verification

Plate to determine the

acceptable range for flow.

Typically, 100 to 110 CFM

is a pass.

Check gauge operation and check for blocked, leaking or

pinched tubes weekly, and anytime results are in question.

To perform the gauge check, you will need the gauge

and Umbilical.

Press [Exit] [Time Average] until “4s” appears.

Press [Mode] repeatedly to display “PrB”.

Connect the yellow tube between the red and

yellow ports.

Repeat between different ports with each of the

tubes you use for testing.

Field check gauge weekly

If readings on “PrA” and “PrB” are within 2% and

don’t drop rapidly, the tube is not blocked or

leaking and the gauge is correct.

Checking your gauge

and tubes regularly will

eliminate a common

source of error in

readings.

Mid-Range Ring

& Low-Range
Ring

(Mid) Part #: DU154

(Low) Part #: DU155

Check the DucTester system monthly with a

known setup―if flow is outside the acceptable

range then system needs full calibration.

Field check system monthly