PD138 Minimux

®

II Temp & Process Scanner

Instruction Manual

7

SPECIFICATIONS

NUMBER OF
CHANNELS PER
MINIMUX

8 double-pole channels per unit

NUMBER OF
CHANNELS PER
SYSTEM

Unlimited

SIGNALS
SWITCHING

DPST reed relays

CONTACT
RESISTANCE

0.2

Ω maximum

MAXIMUM INPUT
VOTAGE

200 V (switched or common mode)

MAXIMUM
CURRENT
SWITCHED

0.5 A

MAXIMUM
POWER
SWITCHED

10 W

DWELL
TIME

Each channel adjustable from 0.6 to 30 seconds

NON-VOLATILE
MEMORY

All programming values are stored in non-volatile
memory for ten years if power is lost

SCAN METHOD

Internal or manually controlled

CHANNEL
INDICATION

Green LED on front panel

DISABLING
CHANNELS

Any channel may be disabled

SCAN STOP

The scan may be stopped by pressing and holding the
STOP/GO button for more than 0.5 seconds. The scan
may be resumed by pressing and releasing the STOP/GO
button quickly (less than 0.5 seconds)

ALARM INPUT

Independent alarm input for each channel. Input
Impedance; 25 Kohm, typical pull-up to 5 V

ALARM
SEQUENCE

Sequence A or Sequence F2A (First-Out)

ALARM OUTPUTS

Alarm condition indicated by:
1.

Front panel red LED for each channel.

2.

Relay, 1 SPDT (form C); rated 2 A @ 30 VDC or 2 A
@ 250 VAC resistive load; 1/14 HP @ 125 / 250
VAC for inductive loads. For fail-safe operation, the
relay is energized in the non-alarm state. In the case
of a power failure, the relay will go to the alarm
state, (NC contact is connected to common).

3.

Built-in horn, 85 dB.

4.

Stop-on-alarmed-channel (user select)