Stop or Continuous Scanning On Alarm

The PD138 can be programmed to either stop or continue scanning
when it encounters a channel in alarm. See page 22 for further details on
this function

DIP

Switch 1

Position

Function

OFF

Continuous scan (Factory Default Setting)

ON Stop-on-alarm

Selecting Alarm Sequence

The PD138 can be programmed to respond to alarm conditions either via
Sequence A or Sequence F2A. Refer to page 26 for a description of
these sequences.

DIP

Switch 2

Position

Alarm Sequence

OFF A

(Factory Default Setting)

ON F2A

Relay Fail-Safe

In fail-safe operation, a relay coil is energized in non-alarm condition. In
case of power failure, relays will go to alarm state.

DIP

Switch 3

Position

Relay Action

OFF Non-Fail-Safe

(Factory Default Setting)

ON Fail-Safe

Note: The power must be cycled after making changes to the fail-safe
operation.