MEDC DB3B User Manual
Page 10

07/14
© MEDC 2014
The unit is fitted with a volume control which is positioned on the top face of the electronics assembly PCB.
Maximum volume is obtained when this control is turned fully clockwise. When turned fully anti-clockwise the unit
will emit no sound.
Warning: Do not attempt to turn the volume control past its limits of movement as this may cause damage to the
unit.
Stages
For all versions, a 5-way DIP switch selects the stage required for each stage. The settings for the standard stages
are shown in the table below:
Tone table 1:
TONE
No.
TONE FREQ/DESCRIPTION
SWITCH
SETTING
12345
TONE DESCRIPTION
Nominal SPL
(dB(A) @ 1m)
1
Alt Stages 800/970 Hz at 1/4 sec
11111
112
2
Sweeping 800/970 Hz at 7 Hz
11110
Fast Sweep (LF)
111
3
Sweeping 800/970 Hz at 1 Hz
11101
Medium Sweep (LF)
113
4
Continuous at 2850 Hz
11100
111
5
Sweeping 2400-2850 Hz at 7 Hz
11011
Fast Sweep
112
6
Sweeping 2400-2850 Hz at 1 Hz
11010
113
7
Slow Whoop
11001
Slow Whoop
113
8
Sweep 1200-500 Hz at 1 Hz
11000
Din Stage
117
9
Alt Stages 2400/2850 Hz at 2 Hz
10111
111
10
Int Stage of 970 Hz at 1 Hz
10110
Back-up Alarm (LF)
112
11
Alt Stages 800/970 Hz at 7/8 Hz
10101
112
12
Int Stage at 2850 Hz at 1Hz
10100
Back-up Alarm (HF)
112
13
970 Hz at 1/4 sec on 1 sec off
10011
112
14
Continuous at 970 Hz
10010
112
15
554 Hz for 0.1S/440 Hz for 0.4S
10001
French Fire Sound
113
16
Int 660 Hz 150 mS on 150 mS off
10000
Swedish Fire Alarm
108
17
Int 660 Hz 1.8 sec on 1.8 sec off
01111
Swedish Fire Alarm
108
18
Int 660 Hz 6.5 sec on 13 sec off
01110
Swedish Fire Alarm
109
19
Continuous 660 Hz
01101
Swedish Fire Alarm
108
20
Alt 554/440 Hz at 1 Hz
01100
Swedish Fire Alarm
113
21
Int 660 Hz at 7/8 Hz
01011
Swedish Fire Alarm
108
22
Int 2850 Hz 150 mS on 100 mS off
01010
Pelican Crossing
111
23
Sweep 800-970 Hz at 50 Hz
01001
Low Freq. Buzz
109
24
Sweep 2400 -2850 Hz at 50 Hz
01000
High Freq. Buzz
111
25
3x970 Hz pulses 0.5 off, 1.5 off
00111
112
26
3x2850 Hz pulses 0.5on/0.5off, 1.5 off
00110
112
27
Int 3100 Hz 0.32s on/0.68s off
00101
105
28
Continuous 1400 Hz
00100
125
29
Spare / Custom tone
00011
30
Spare / Custom tone
00010
31
Spare / Custom tone
00001
32
Spare / Custom tone
00000
Note: If special tones were requested at the time of ordering, please see the separate tones list supplied with the unit
for details of these special tones and their respective switch settings.
4.0 OPERATION
The sounder is available in various AC input voltage versions and a single DC input voltage version.
For AC versions, the nominal operating voltage is stated on the unit label and the supply voltage tolerance is ±10%.
For DC versions, the absolute input voltage range is 11.0Vdc to 57.6Vdc.
If using an EOL resistor with a value between 700Ω and 2KΩ the maximum voltage should be limited to 28.8Vdc, if
using an EOL resistor with a value between 470Ω and 700Ω the maximum voltage should be limited to 26Vdc.