MEDC XB10 User Manual
Page 6

12/11
© Cooper MEDC 2011
Ex de unit (ATEX certification No. BAS00ATEX2226X)
10J:- Ex de IIB T4 (-50°C to +65°C) Gb
15J:- Ex de IIB T4 (-50°C to +50°C) Gb
The ATEX certificate and product label carry the ATEX group and category marking:
II 2 G
Where:
Signifies compliance with ATEX
II
Signifies suitability for use in surface industries
2
Signifies suitability for use in a zone 1 area
G
Signifies suitability for use in the presence of gases
The ATEX certificate and product label also carry the following mark:
This signifies unit compliance to the relevant European directives, in this case 94/9/EC, along with the number
of the notified body issuing the EC type examination certificate.
6.0 SPECIAL CONDITIONS FOR SAFE USE
a. Exd units: Certificates BAS00ATEX2204X & IECEx BAS 10.0086X
1. The mating thread of any cable entry device unused with this apparatus must exceed 12mm in length
2. Painting and surface finishes, other than those applied by the manufacturer, are not permitted
b. Exde units: Certificates BAS00ATEX2226X & IECEx BAS 10.0087X
1. Not more than one single or multiple strand lead shall be connected into either side of any terminal, unless
multiple connectors have been joined in a suitable manner, e.g. two conductors into a single insulated
crimped boot lace ferrule.
2. Leads connected to the terminal shall be insulated for the appropriate voltage and this insulation shall
extend to within 1mm of the metal of the terminal throat.
3. All terminal screws, used and unused, shall be fully tightened down.
4. Minimum creepage and clearance distances between the terminals and adjacent conductive parts
(including cable entry devices) must be at least 5mm.
5. Painting and surface finishes, other than those applied by the manufacturer, are not permitted
These units also have the following approvals
Main Harmonics (AC) to EN61000-6-3:2007 / IEC61000-3-2:2006
Conducted Emissions (DC) to EN61000-6-3:2007
Radiated Field Immunity (DC and AC) to EN61000-6-2:2005 / IEC61000-4-3:2002 + A1:2002
Electrical Fast Transients/Bursts (DC and AC) to EN61000-6-2:2005 / IEC61000-4-4:2004
Dips and Interruptions (AC) to EN61000-6-2:2005 / IEC61000-4-11:2004
Ingress protection IP66 to BS EN 60529:1992
Ingress protection IP67 to BS EN 60529:2001