beautypg.com

Eaton Electrical 34003991EN/EB User Manual

Page 66

background image

Network Management Card

– User Manual

34003991EN/EB

Page

66/118

Start of the shutdown sequence

Delay before

shutdown

Utility failure

Remaining autonomy

100%

Shutdown after :

If remaining time under

UPS Shut off

Card parameters

UPS parameters

Shutdown duration

Battery

capacity

0%

Shutdown if

remainig

capacity under

t

5.1.1.1 Backup time before initiating the shutdown procedure

(Shutdown After – Shutdown Timer)

When the UPS switches to battery, the Network Management Card starts the Shutdown Timer countdown and launches

the system shutdown procedure at the end of the countdown.

This value must be chosen so that users have time to complete their tasks and disconnect, without exceeding battery

backup time.

Note 1:

The Network Shutdown Module can also manage its own Shutdown Timer (configurable in the Shutdown Module"set-

up" menu of each Network Shutdown Module) launched when the UPS switches to battery.

Note that if this criterion is selected to initiate system shutdown, automatic system reboot when power is restored is

not guaranteed (e.g. power restoration if only this system was shut down).

5.1.1.2 Initiating the shutdown procedure when the battery level is lower than:

(If Capacity under)

When the card detects that the remaining backup time percentage is less than the configured level, the shutdown

sequence is started.

By default, this value is set at 20%.

Note:

The UPS already manages an equivalent parameter for the end of backup pre-alarm.

The card does not accept values less than that programmed in the UPS.

Check the UPS documentation.