Ethernet port
LED
Colour
Activity
Description
ACT
Green
◗
Off
◗
Card not connected to the network.
◗
On
◗
Card connected to the network but
without activity
◗
Flashing
◗
Port is active in receiving /
transmission
100M
Orange
◗
Off
◗
Port operating at 10Mbits/s.
◗
On
◗
Port operating at 100Mbits/s.
Service port
LED
Colour
Activity
Description
UPS
Green
◗
Off
◗
Card startup in progress.
Data
◗
On
◗
Communication with UPS in
progress
◗
Flashing
◗
Normal operation.
Communication with the UPS is
operational
RS232
Orange
◗
Off
◗
Configuration menu is active
◗
On
◗
Normal operation. Configuration
menu is deactived
◗
Flashing
◗
Communication with the
Environment Sensor (option).
2.3 Installation in the UPS
The Network Management Card (66102) can be "hot" installed in all UPSs of the MGE Office Protection Systems or
Powerware range equipped with a Minislot without having to shut it down.
◗
Remove the protective plastic cover from the Minislot
◗
Note the card's MAC address prior to insertion
◗
Insert and tighten the card's retaining screws
◗
Connect the ETHERNET cable
◗
Wait 2 min. the card is completely operational when the green UPS Data LED flashes continuously