beautypg.com

General specifications – Emerson AccuVar NEMA 4X User Manual

Page 2

background image

EMI/RFII Filtering

65 KA Modules or

80 KA Modules

Metal Oxide Varistor Array (MOV’s)

Housing

UL94-5V and

NEMA 4X Rated

Silver Fuse Links

Liebert Corporation

1050 Dearborn Drive

P.O. Box 29186

Columbus, Ohio 43229

800 877 9222 Phone (U.S. &

Canada Only)

614 888 0246 Phone (Outside U.S.)

614 841 6022 FAX

Via Leonardo Da Vinci 8

Zona Industriale Tognana

35028 Piove Di Sacco (PD)

Italy

39 049 9719 111 Phone

39 049 5841 257 FAX

Emerson Network Power Asia Pacific

7/F., Dah Sing Financial Centre

108 Gloucester Rd, Wanchai

Hong Kong

852 25722201 Phone

852 28029250 FAX

liebert.com

Technical Support

607 724 2484 Phone

800 288 6169 Toll-Free

607 722 8713 Fax

While every precaution has been taken to ensure accuracy

and completeness in this literature, Liebert Corporation assumes

no responsibility, and disclaims all liability for damages resulting

from use of this information or for any errors or omissions.

© 2005 Liebert Corporation. All rights reserved throughout

the world. Specifications subject to change without notice.

All names referred to are trademarks or registered

trademarks of their respective owners.

® Liebert and the Liebert logo are registered trademarks

of the Liebert Corporation.

SL-22040 (R9/05) Printed in USA

Emerson Network Power.

The global leader in enabling

business-critical continuity.

AC Power Systems

Connectivity

DC Power Systems

Embedded Power

Inbound Power

Integrated Cabinet Solutions

Outside Plant

Precision Cooling

Site Monitoring and Services

Emerson Network Power and the Emerson

Network Power logo are trademarks and

service marks of Emerson Electric Co.

©2005 Emerson Electric Co.

Maximum Safety:

The modules used in the Liebert AccuVar System are UL tested at 600

VAC and 200,000 AIC. Each MOV inside the module is individually fused

and matched to within 1 Volt to ensure maximum sharing and full

surge current handling capability. These 99.9% pure silver links are

ultrafast clearing providing minimal follow current in the

event failure occurs.

General Specifications

Connection Means:

Parallel connected

Agency Listings:

UL1449, UL1283, CSA, CE Available

Protection Modes:

All modes standard (L-N, L-G, N-G, L-L)

optional—any combination

Surge Current Rating:

ACV 65 KA/Mode, 130 KA/Phase

ACV II 80 KA/Mode, 160 KA/Phase

EMI/RFI Attenuation:

60 dB typical

Response Time:

Less than .5 ns

Operating Frequency:

47/63 Hz

Enclosure:

Gray Noryl HS-1000, Rated 94-5V,

NEMA, 12, 4, 4X

Short Circuit Current Rating:

200,000 AIC

Line Frequency:

47–63 HZ

Line Voltage:

+/–15% nominal

Temperature:

–40 to +60 degrees C

Relative Humidity:

0 to 95% noncondensing

Altitude:

0 to 18,000 feet

Audible Noise:

Less than 45 dBa

Standard Monitoring:

LEDs and Audible Alarm